Battery storage rules: Village of Pleasant Prairie, WI

Last checked against primary sources: October 28, 2026

Village of Pleasant Prairie Ordinance #26-21 (adopted April 27, 2026) makes utility-scale battery storage (5 MW or more) a conditional use in the M-4 Power Generating District only, on a lot of at least 10 acres, not in the floodplain, with a 15-foot height limit for any battery storage unit. It must be designed, built, operated, maintained and decommissioned to meet NFPA 855, with a hazard mitigation analysis and an emergency response plan approved by the village, any approvals required from the Public Service Commission provided to the village, and a bond for removal.

Pleasant Prairie: battery storage allowed only as a conditional use in the M-4 district (April 2026)

Ordinance #26-21 (April 27, 2026) makes utility-scale battery storage a conditional use in the M-4 Power Generating District, with NFPA 855 design and operation and a village-approved hazard mitigation analysis and emergency response plan. Village of Pleasant Prairie Ord. #26-21

Fire and building codes in force

How a project is permitted

Local zoning decides where battery storage goes: the county, city or village, or the town where there is no county zoning (Wis. Stat. 59.69, 60.61, 62.23). Wis. Stat. 196.491 requires a Public Service Commission certificate of public convenience and necessity before construction of a "large electric generating facility", "electric generating equipment and associated facilities designed for nominal operation at a capacity of 100 megawatts or more" (196.491(1)(g), (3)(a)). The statute does not mention battery storage. The PSC's filing requirements for energy storage projects (April 7, 2026) say: "Proposed projects that would be large electric generating facilities as defined in Wis. Stat. § 196.491(1)(g) require a Certificate of Public Convenience and Necessity (CPCN) from the PSC." They also ask applicants to "Provide evidence to demonstrate the proposed project would comply with NFPA 855, UL 9540 testing protocols for battery systems." Wis. Stat. 196.491(3)(i) says: "If installation or utilization of a facility for which a certificate of convenience and necessity has been granted is precluded or inhibited by a local ordinance, the installation and utilization of the facility may nevertheless proceed." Ask: is the battery 100 megawatts or more, and has the developer filed with the PSC? Ask the PSC whether it needs a certificate, and how a certificate and 196.491(3)(i) apply to your local rules. Does my county have general zoning, and is my town under it? Which fire code does my fire department enforce, and does the state fire code reach an outdoor battery yard? Ask your fire chief or the Department of Safety and Professional Services.

State permits and reporting rules that may apply

Setbacks and spacing

Sources

Check a specific system

For a proposal or a system you're evaluating, answer a few questions in BESScheck: you get the rules that apply here, a checklist of what to ask, and the sources behind each line.